Video: How do you set up the ATV61/71 drive so that the set point for PID can be adjusted using the keypad?

Article available in these languages: Spansk

Issue:
Trying to set up the ATV61/71 drive so that the set point for PID can be adjusted using the keypad.

Product Line:
ALTIVAR 61, ALTIVAR 71

Environment:
All serial numbers

Resolution:
In the PID Regulator function, set parameter "Act. Internal PID ref" to NO.  Use "Ref 1 channel" set to HMI.