Background:
There used to be the hooker issue on eth module/cpu copro by which the comm. process hooks the interaction with CPU endlessly during net broadcast storm. In this situation, the CPU is likely to go HALT due to run time overrun.
Question:
What is the least version of Ethernet module to solve the CPU hooker issue?
Answer:
Addressed by OPR20040135, the least version of Ethernet module to solve the CPU hooker issue is as indicated below---
Q-NOE V4.3
ETY V4.1
CoPro V2.6
There used to be the hooker issue on eth module/cpu copro by which the comm. process hooks the interaction with CPU endlessly during net broadcast storm. In this situation, the CPU is likely to go HALT due to run time overrun.