Why is the dynamic braking resistor repeatedly failing in our lift application?

Issue:
Why is the dynamic braking resistor repeatedly failing in our lift application?

Product Line:
Dynamic braking resistors, Altivar 71

Environment:
Lifting applications

Cause:
DBR failure

Resolution:
Generally, the dynamic braking resistors burning or failure happens due to higher braking energy dissipation than it's power rating.
If you select the normal braking resistor part reference provided in the catalog, the power rating of the resistor is insufficient to dissipate the braking energy generated by the motor in during downward movement. Hence it will burn the resistor due to overheating.

The lift is a vertical and cyclic movement application, and the braking power dissipation is similar to hoisting application. Hence it is necessary to select the hoisting resistor part references provided in the ATV71 catalog to avoid DBR failure due to overbraking.

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger