Issue:
Smaller horsepower motor on a larger horsepower Soft Starter
Product Line:
Altistart series
Environment:
All serial numbers for Altistart series
Cause:
N/A
Resolution:
YES.
In most cases a soft starter can control a motor with lower HP (and current) rating.
The motor FLA information will have to be entered correctly to ensure proper control of the motor and that the overload protection is activated.
In most cases the Overload protection adjustment range is the limiting factor. If this parameter can not be set down to the motor FLA, an external overload relay will have to be provided.
Smaller horsepower motor on a larger horsepower Soft Starter
Product Line:
Altistart series
Environment:
All serial numbers for Altistart series
Cause:
N/A
Resolution:
YES.
In most cases a soft starter can control a motor with lower HP (and current) rating.
The motor FLA information will have to be entered correctly to ensure proper control of the motor and that the overload protection is activated.
In most cases the Overload protection adjustment range is the limiting factor. If this parameter can not be set down to the motor FLA, an external overload relay will have to be provided.