How to Write a number to 3nnnn register in SCADAPack with TelePACE firmware?

The 30000-class register table is for Input Registers and is read-only to external Modbus masters. If you need a writable target over Modbus, use 40000-class table for Holding Registers.

That being said, you can have TelePACE ladder logic push data into a 3nnnn register if required. Using the OVER function block in TelePACE Studio, a register value can be written into a 3nnnn register . The source register can be any valid 0nnnn (coil register), 1nnnn (status register), 3nnnn (input register) or 4nnnn (holding register)

Please note: Using the OVER block will override the value in the destination input register. This is considered a force in the controller and will turn on the SCADAPack's FORCE LED .

Schneider Electric Danmark

Se mere
Produkt:
Se mere
Produkt:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger