Can an analog input be used for the PID reference with the Altivar Process Drive?
Issue:
Analog input usage for the PID reference with the Altivar Process Drive
Product Line:
ATV 600/900 series
Environment:
All models, All serial numbers
Cause:
Customer has an application with a dynamic setpoint and needs to use 4-20ma input for the PID reference.
Resolution:
Yes, If parameter PII (Internal PID Reference) is set to NO, the drive will use the Reference 1 channel as the PID reference. Reference 1 channel can be configured for any analog input.
Analog input usage for the PID reference with the Altivar Process Drive
Product Line:
ATV 600/900 series
Environment:
All models, All serial numbers
Cause:
Customer has an application with a dynamic setpoint and needs to use 4-20ma input for the PID reference.
Resolution:
Yes, If parameter PII (Internal PID Reference) is set to NO, the drive will use the Reference 1 channel as the PID reference. Reference 1 channel can be configured for any analog input.