How do we ACK alarms on an HMI from a PLC bit?

Issue:
Looking for a way to programmatically ACK alarm on the HMI from a PLC bit.

Product Line:
Vijeo Designer, Vijeo Designer Runtime

Resolution:
To allow a PLC bit to ACK all alarms displayed in the Alarm Summary, the following script call should be made in a Panel Action (on the same panel as the Alarm Summary).

<Alarm Group name>.ackAll();

Note: The action should be configured as Conditional and to execute when the PLC bit is "True".

The attached project makes use of a Panel Action that executes an AlarmGroup script when a PLC bit is "True".

Please see the attached project for the example.

Schneider Electric Danmark

Bilag
RemoteAckFromPLC.zip [55.14 KB]
Se mere
Område:
Se mere
Område:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger