Vores varemærker

Impact-Company-Logo-English Black-01-177x54

Velkommen til Schneider Electrics website

Velkommen til vores website
		
Hvordan kan vi hjælpe dig i dag?
What is the consumption of LC1D50** contactor with 220VDC coil control supply?
The inrush and sealed consumption is mentioned in the catalog and datasheets.

The contactor LC1D50**** with DC control supply, the consumption given below and it is same for all DC voltage ranges from 12VDC to 440VDC.

Inrush power - 19W at 20 °C
Hold-in power consumption - 7.4W at 20 °C

Please refer the attached catalog page and datasheet for your reference. The specific information is highlighted for your information.

Schneider Electric Danmark

Bilag
LC1D50AMD - 220VDC.pdf [72.29 KB]
Tesys D contactor - DC control supply.pdf [103.58 KB]
Se mere
Område:
Se mere
Område:

Brug for hjælp?

  • Produktvælger

    Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

  • Få et tilbud

    Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

  • Find forhandler

    Find den nærmeste Schneider Electric-distributør.

  • Hjælpecenter

    Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Få et tilbud
  • Find vores kontorer
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger