When attempting to open a 3300 ACM in Designer to configure the meter, the system prompts the following error and results in a crash.
Product Line
StruxureWare Power Monitoring Expert
Environment
Power Monitoring Expert 8.1
Cause
Designer crashes as a result of the ACM 3300 meter returning "330" for its Device type rather than "3300".
Resolution
**Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).
A patch is available to resolve this issue within Designer. (set3300.zip attached below)
To deploy this patch, please perform the following:
- Make a backup copy of set3300.dat, which you will find in the following folder: <PME installation folder>\system\etc
- E.g. C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\etc\set3300.dat
- Copy the new version of set3300.dat over top of the original version.
*It is expected that support for the 3300 in Designer will be phased out in a future software release.