Does OFS recognize the bit rank of a DDT (Derive Data Type)?
Issue:
Does OFS recognize the bit rank of a DDT (Derive Data Type)?
Product Line:
OPC Factory Server
Resolution:
OFS does not support bit ranks of a DDT. Unity is not able to export the overloaded comments of DDT members instance (bit rank). It was to make the data dictionary as light as possible.
Two possible workaround :
- access the extracted bit via the complete syntax ddt_inst.int.bit
- move the Bit rank to a Bool variable
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.