What can cause on OC1 fault on the ATV21 and ATV212 drives?
Issue:
OC1 fault on ATV21 and ATV212 drives
Product Line:
Altivar ATV21 and ATV212
Environment:
All
Cause:
Over current during acceleration
Resolution:
Increase the ACC time or the ACC2 time
Try adjusting the PT parameter
Enable catch on the fly F301= 4
Try adjusting the switching frequency F300
Set F316 parameter to 1 or 3
OC1 fault on ATV21 and ATV212 drives
Product Line:
Altivar ATV21 and ATV212
Environment:
All
Cause:
Over current during acceleration
Resolution:
Increase the ACC time or the ACC2 time
Try adjusting the PT parameter
Enable catch on the fly F301= 4
Try adjusting the switching frequency F300
Set F316 parameter to 1 or 3