What are the Sepam 40 & 80 firmware requirements for setting up the ACE850TP / ACE850FO
Issue
Need to determine whether an existing Sepam Series 40 or Series 80 supports TCP/IP communication through an ACE850TP or ACE850FO.
Product Line
Sepam Series 40
Sepam Series 80
ACE850TP
ACE850FO
Environment
Ethernet communication
Modbus TCP/IP
Cause
ACE850 compatibility depends on the Sepam firmware version and the installed TCP/IP firmware option.
Resolution
The minimum firmware requirements are:
| ACE850 (TP/FO) | Version OK |
| Sepam Series 40 | V7.00 or Greater |
| Sepam Series 80 | Base & Application V6.00 or Greater |
The TCP/IP firmware option, reference 59754, must also be present on the Sepam relay.
The ACE850TP and ACE850FO are not compatible with Sepam Series 20.
For IEC 61850 applications, verify the separate protocol-specific firmware and hardware requirements.
Note: That the ACE850 cannot be used with the Sepam 20 series.