Issue:
Turning off the flashing red caution LED on the ATV630 and ATV930 process drives.
Product Line:
Altivar ATV630 and ATV930
Environment:
All
Cause:
There is a default alarm set in the warnings group for Analog input AI1, AI2, and AI3 that has to be turned off.
Resolution:
The warning LED is triggered when a Warning Group item is activated. The factory default has many items selected for monitoring under Warning Group 1. A typical warning is caused when an analog input is configured for 4-20mA, but the signal is not present.
From the Main menu:
See attachment
Now the red flashing warning light will turn off.
Turning off the flashing red caution LED on the ATV630 and ATV930 process drives.
Product Line:
Altivar ATV630 and ATV930
Environment:
All
Cause:
There is a default alarm set in the warnings group for Analog input AI1, AI2, and AI3 that has to be turned off.
Resolution:
The warning LED is triggered when a Warning Group item is activated. The factory default has many items selected for monitoring under Warning Group 1. A typical warning is caused when an analog input is configured for 4-20mA, but the signal is not present.
From the Main menu:
- Scroll to Complete Settings and press OK
- Select Error Warning Handling and press OK
- Select Warnings Group Configuration and press OK
- Select Warn group 1 definition and press OK
- Now (almost halfway down the list) uncheck "AI1 4-20 Warning", "AI2 4-20 Warning", and "AI3 4- 20 Warning" boxes.
See attachment
Now the red flashing warning light will turn off.
Udgivet til: Schneider Electric Danmark




Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.