ATV630 series drives, How do I bring the total input impedance up to 5%? The drive catalog shows 3% internal impedance already, do we add a 2% reactor?

Issue:
The ATV630 series drives have 3% impedance standard, is there a way to bring that up to 5%?

Product Line:
ATV600 series process drives.

Environment:
All models, All serial numbers

Cause:
Information unavailable in current literature.

Resolution:
In order to bring the equivalent input impedance of the ATV600 series drives to 5%, add a 3% line reactor ahead of the drive, not 2%. The input impedance is not linear so a 2% reactor added to the 3% internal equivalent impedance will not yield 5% input impedance.

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger