Issue
What is the COMTRADE file name/time format, and can it be changed?
Product Line
PowerLogic PM8000 Series
Environment
COMTRADE File
Resolution
The COMTRADE files (.cfg and .dat) from a sag/swell or transient event can be found on the PM8000's FTP site.
Q: The COMTRADE file is generated with my local time, can this be changed?
A: Yes, the timestamp can be changed inside the file.
Q: Is that possible to customize the COMTRADE file name?
A: No, the file name cannot be altered (typically called cmt0__00000 (incrementing with each new saved waveform) and documented in .cfg and .dat formats).
Example of COMTRADE .cfg output:

Please follow the attached COMTRADE & ION Technology document for steps on enabling the COMTRADE feature (disabled by default).
*Note: a master reset will clear all COMTRADE files on the FTP site.*
What is the COMTRADE file name/time format, and can it be changed?
Product Line
PowerLogic PM8000 Series
Environment
COMTRADE File
Resolution
The COMTRADE files (.cfg and .dat) from a sag/swell or transient event can be found on the PM8000's FTP site.
Q: The COMTRADE file is generated with my local time, can this be changed?
A: Yes, the timestamp can be changed inside the file.
Q: Is that possible to customize the COMTRADE file name?
A: No, the file name cannot be altered (typically called cmt0__00000 (incrementing with each new saved waveform) and documented in .cfg and .dat formats).
Example of COMTRADE .cfg output:
Please follow the attached COMTRADE & ION Technology document for steps on enabling the COMTRADE feature (disabled by default).
*Note: a master reset will clear all COMTRADE files on the FTP site.*
Udgivet til: Schneider Electric Danmark


Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.