Why does LTU have some errors when performing automatic tests with LTU and Maintenance Tool on NSX?

LTU has a known limitation when configuring some automatic tests with Maintenance Tool (TRV00911).  This is a result of the pre-setting being different when automatic mode is performed.  As a result, the tests in automatic mode does not have a large enough injected current to trigger the short time protection for some settings.
In this situation, the test will show a false FAIL result.

Example screen shot with failed result:


Workaround: Perform the same testing in manual mode as this uses a different group of settings.
If the same test is done with manual mode, the results will return with a PASS.

Example screen shot with the manual test configuration:



Example screen shot with the manual test test results:

Schneider Electric Danmark

Bilag
FA305808 LTU Fault on automatic test.pdf [271.51 KB]

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger