Issue:
ATV320 2-wire control programming
Product Line:
Altivar 320, ATV320
Environment:
All
Cause:
Setup, programming.
Resolution:
From main menu:
If desired, set TCT to LEL instead of TRN for level control.
Warning: Level control type is not appropriate for all applications. Please consider whether this is safe for your application.
-In transition mode (trn), the drive will need to be powered up before a run command is given.
-In level mode (LEL), the run command can remain active, and the drive will run upon power up.
If the run command is not active, the drive will wait for one in RDY status.
ATV320 2-wire control programming
Product Line:
Altivar 320, ATV320
Environment:
All
Cause:
Setup, programming.
Resolution:
From main menu:
- Enter on dial to go to CONF and enter.
- Go down to FULL and enter.
- Go down to I_0- and enter.
- Set TCC for 2C for 2-wire control.
If desired, set TCT to LEL instead of TRN for level control.
Warning: Level control type is not appropriate for all applications. Please consider whether this is safe for your application.
-In transition mode (trn), the drive will need to be powered up before a run command is given.
-In level mode (LEL), the run command can remain active, and the drive will run upon power up.
If the run command is not active, the drive will wait for one in RDY status.
Udgivet til: Schneider Electric Danmark


Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.