Issue
Assigning Different Modbus Addresses for each COM Port in the Slave SCADAPack
Product Line
SCADAPack E RTU
Environment
Windows OSes, E Configurator
Resolution
The Resolution Provides detailed steps in E Configurator Software to assign different Modbus addresses to COM Ports in SACADAPACK 535E
1- Install E Configurator 8.12.5
2- Update the SP535E to latest Firmware Version 8.12.5
3- In the Port 0-3 page in case of 300E Series or Port 0-4 in case of 500E Series, Configure The Serial Ports with the Modbus settings to be matched with the Modbus Master, an example is below
4- In the Point Browser page, Add 5 Analog System Points to be configured
Where:
Address | Description |
---|---|
52014 | System Point |
52017 | Port 1 Modbus Address |
52018 | Port 2 Modbus Address |
52019 | Port 3 Modbus Address |
52020 | Port 4 Modbus Address |
5- Write the Following Values to assign different Modbus Addresses to Port 1 & Port 2
Port Address | Value |
---|---|
52014 | 0 |
52017 (Port 1) | 1 |
52017 (Port 2) | 2 |
7- Perform the Power Cycle the SCADAPack
8- Use Read to check if the new addresses were applied
9- Configure the Modbus Master Address with Value 1 and Connect the Serial Cable between The Modbus Master device and Port 1 of SCADAPack Slave Device.
10- Check that the Communication is good when Tx &Rx LEDs of COM1 are blinking.
11- Move the Serial Cable to Port 2; The Communication will be lost until you change the Modbus Master address to Value 2
Udgivet til: Schneider Electric Danmark








Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.