Issue:
The ATV32 drive has a blank display and will not power up.
Product Line:
ATV32 drives
Environment:
All
Cause:
Power board appears to be inoperative.
Resolution:
If the Display is blank there are some troubleshooting checks to do.
1) Check to see if you have line voltage L1 L2 L3 on the input of the drive.
2) Check the DC bus on PA to PC if it applies. DC bus voltage should be Line voltage times Square root of 2.
3) Check the + 10vdc and +24vdc power supplies.
4) Remove all control wires from the drive to make sure nothing is pulling down the DC voltage supplies.
If the drive is inoperative, you will need to replace the drive.
The ATV32 drive has a blank display and will not power up.
Product Line:
ATV32 drives
Environment:
All
Cause:
Power board appears to be inoperative.
Resolution:
If the Display is blank there are some troubleshooting checks to do.
1) Check to see if you have line voltage L1 L2 L3 on the input of the drive.
2) Check the DC bus on PA to PC if it applies. DC bus voltage should be Line voltage times Square root of 2.
3) Check the + 10vdc and +24vdc power supplies.
4) Remove all control wires from the drive to make sure nothing is pulling down the DC voltage supplies.
If the drive is inoperative, you will need to replace the drive.
Udgivet til: Schneider Electric Danmark


Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.