What is the CFI2 fault on an Altivar (ATV600, ATV900 and ATV340) drive?
Issue:
Customer has the CFI2 fault on an Altivar Process Drive
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980, and APM)
Altivar Machine Drive (ATV340)
Environment:
All serial numbers
Cause:
N/A
Resolution:
The CFI2 is Configuration Transfer Error Fault.
Occurs when a configuration file can not be loaded to the device, or the configuration is not compatible with the drive.
Possible Causes:
Customer has the CFI2 fault on an Altivar Process Drive
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980, and APM)
Altivar Machine Drive (ATV340)
Environment:
All serial numbers
Cause:
N/A
Resolution:
The CFI2 is Configuration Transfer Error Fault.
Occurs when a configuration file can not be loaded to the device, or the configuration is not compatible with the drive.
Possible Causes:
- The was an unsuccessful or interrupted configuration file transfer.
- The stored configuration (HMI) was loaded from an different firmware. For example a file saved on a newer version drive can not be loaded into an older firmware version.
- Check firmware
- Firmware should be compatible on both drives
- Load a compatible configuration.
- Use SoMove to transfer configuration from another drive, or modify the saved SoMove configuration to match the drive being programmed.
- Perform a factory setting
- [Main Menu] [File Transfer] [Factory Settings]
Udgivet til: Schneider Electric Danmark






Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.