Issue:
The ATV71 has External Fault assigned to LI5. When active, LI5 trips the drive into External Fault, EPF1. When activating Fault Reset on assigned LI4, the fault is not reset.
Product line:
Altivar 61 Altivar 71
Environment:
All
Cause:
The fault reset needs to come from the assigned Command Channel.
Resolution:
In this case, Command Channel 1 was assigned to a Communications network. So, a Fault Reset needs to come from the Communications Network.
Fault reset by Logic Input is not possible unless the active command channel is Terminals.
Consider temporarily switching the Command Channel to Terminals and then close Logic Input assigned to Reset, or switch to HMI mode and use the local Stop/Reset button (push twice) to reset.
See description / options on the attached file.
The ATV71 has External Fault assigned to LI5. When active, LI5 trips the drive into External Fault, EPF1. When activating Fault Reset on assigned LI4, the fault is not reset.
Product line:
Altivar 61 Altivar 71
Environment:
All
Cause:
The fault reset needs to come from the assigned Command Channel.
Resolution:
In this case, Command Channel 1 was assigned to a Communications network. So, a Fault Reset needs to come from the Communications Network.
Fault reset by Logic Input is not possible unless the active command channel is Terminals.
Consider temporarily switching the Command Channel to Terminals and then close Logic Input assigned to Reset, or switch to HMI mode and use the local Stop/Reset button (push twice) to reset.
See description / options on the attached file.
Udgivet til: Schneider Electric Danmark




Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.