What would cause the ATV61 drive mounted inside a MCC to show a PRA drive status only when the HOA is in auto mode?

Issue:
What would cause the ATV61 drive mounted inside a MCC to show a PRA status?

Product Line:
ATV61 MCC

Environment:
All with HOA

Cause:
HOA was miswired PWR input was wired to LI3 auto manual and HOA was wired to PWR input

Resolution:
Troubleshoot this circuit by checking the status of PWR input.  In this case the HOA was wired in error to the PWR input. So the Drive is Rdy in hand and off but goes to PWR when they switch to Auto.
Moved the wire from LI3 to PWR and from PWR to LI3
Now it works.
circuit diagram

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger