Issue: IO1 Input 5 configuration getting set to "none" while configuring Dual settings Selection A/B (1 wire) through Ecoreach.
Product Line: IO Module, Ecoreach.
Cause: Currently, every time a user assigns Dual Setting A/B (1 Wire) to Input #6, Ecoreach deliberately overrides the assignment for Input #5 to avoid possible conflicts between Inputs 5 and 6.
Resolution: Once Input #6 has been assigned to Dual Setting A/B (1 Wire), please configure the assignment for Input #5.
Product Line: IO Module, Ecoreach.
Cause: Currently, every time a user assigns Dual Setting A/B (1 Wire) to Input #6, Ecoreach deliberately overrides the assignment for Input #5 to avoid possible conflicts between Inputs 5 and 6.
Resolution: Once Input #6 has been assigned to Dual Setting A/B (1 Wire), please configure the assignment for Input #5.