How to Configure a Third Stage of Neutral Voltage Displacement Protection (59N) on a Powerlogic P3 protection relay

Issue

The device provides only two dedicated stages of neutral voltage displacement (59N), but the customer requires three stages.

Product

Powerlogic  P3 protection relay

Environment

Protection function configuration – Neutral Voltage Displacement (59N)

Cause

The standard protection package includes only two predefined 59N stages. Additional stages must be configured manually using programmable protection stages.

Resolution

To add a third 59N stage:

  1. Activate one of the eight programmable stages available in the device.
  2. Set the input coupling to Uo.
  3. Configure the threshold and settings in the same manner as one of the dedicated 59N stages.
  4. Save and apply the configuration.

This provides functionality equivalent to an additional 59N stage.

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger