Issue:
ATV61 or ATV71 in MCC configure Hand Off-Auto Selector for Ethernet Control.
Product Line:
Altivar 61 Altivar 71 ATV61 ATV71
Cause:
Configuration
Environment:
Schneider Electric Motor Control Center
Resolution:
Forced Local is programmed from the factory and the IP Address goes away when the Forced Local contact is On.
Program as follows to prevent this;
Command Menu
Ref 1 channel: Com Card (Auto)
Profile: Separate or I/O (*Depends on PLC Assemblies)
(**Note: If you set Profile to I/O, then need to change back, the drive is reset to factory settings)
Cmd Ch1: Com Card
Cmd Ch2:Terminals
Cmd Switching: LI3
Ref 2 Sw: LI3
Ref 2 Ch: AI1 (Hand)
Communications Menu
Forced Local
Forced Local Assignment and Reference - Change to NO
ATV61 or ATV71 in MCC configure Hand Off-Auto Selector for Ethernet Control.
Product Line:
Altivar 61 Altivar 71 ATV61 ATV71
Cause:
Configuration
Environment:
Schneider Electric Motor Control Center
Resolution:
Forced Local is programmed from the factory and the IP Address goes away when the Forced Local contact is On.
Program as follows to prevent this;
Command Menu
Ref 1 channel: Com Card (Auto)
Profile: Separate or I/O (*Depends on PLC Assemblies)
(**Note: If you set Profile to I/O, then need to change back, the drive is reset to factory settings)
Cmd Ch1: Com Card
Cmd Ch2:Terminals
Cmd Switching: LI3
Ref 2 Sw: LI3
Ref 2 Ch: AI1 (Hand)
Communications Menu
Forced Local
Forced Local Assignment and Reference - Change to NO
Udgivet til: Schneider Electric Danmark
Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.