How do I configure an ATV61 or ATV71 in MCC for Ethernet Control with a Hand-Off-Auto Selector?

Issue:
ATV61 or ATV71 in MCC configure Hand Off-Auto Selector for Ethernet Control.

Product Line:
Altivar 61 Altivar 71 ATV61 ATV71

Cause:
Configuration

Environment:
Schneider Electric Motor Control Center

Resolution:
Forced Local is programmed from the factory and the IP Address goes away when the Forced Local contact is On.
Program as follows to prevent this;
Command Menu
Ref 1 channel: Com Card (Auto)
Profile: Separate or I/O (*Depends on PLC Assemblies)
(**Note:  If you set Profile to I/O, then need to change back, the drive is reset to factory settings)
Cmd Ch1: Com Card
Cmd Ch2:Terminals
Cmd Switching: LI3
Ref 2 Sw: LI3
Ref 2 Ch:  AI1 (Hand)

Communications Menu
Forced Local
Forced Local Assignment and Reference - Change to NO

Schneider Electric Danmark

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger