Issue:
How do I setup communication between the Controller and HMI and link the variables.
Product Line:
M238, M241, M251, M258
HMIGTO, HMIG3U
Environment:
SoMachine V4.3
Vijeo XD 3.0
Resolution:
Vijeo XD V3.0 is not integrated with SoMachine V4.3
You have to create a separate SoMachine application for the M251 controller and a separate Vijeo XD V3.0 application for the Magelis HMI.
In Vijeo XD, use the SoMachine Network driver under Schneider Electric. Copy the Node name from the SoMachine application.
Create a symbol link and browse for the application name XML file to import the tags from SoMachine to Vijeo XD. This file is created during a download in SoMachine.
How do I setup communication between the Controller and HMI and link the variables.
Product Line:
M238, M241, M251, M258
HMIGTO, HMIG3U
Environment:
SoMachine V4.3
Vijeo XD 3.0
Resolution:
Vijeo XD V3.0 is not integrated with SoMachine V4.3
You have to create a separate SoMachine application for the M251 controller and a separate Vijeo XD V3.0 application for the Magelis HMI.
In Vijeo XD, use the SoMachine Network driver under Schneider Electric. Copy the Node name from the SoMachine application.
Create a symbol link and browse for the application name XML file to import the tags from SoMachine to Vijeo XD. This file is created during a download in SoMachine.
Udgivet til: Schneider Electric Danmark




Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.