Vores varemærker

Impact-Company-Logo-English Black-01-177x54

Velkommen til Schneider Electrics website

Velkommen til vores website
		
Hvordan kan vi hjælpe dig i dag?
How does one program the ATV212 Drive so that RY relay will trigger when a speed threshold is reached?
Issue:
ATV212 configuration so that RY relay will trigger when a speed threshold is reached

Product Line:
Altivar 212

Environment:
All

Cause:
Frequency reference reached

Resolution:
Using RY relay for speed reached functionality.
F130 from the factory is already programmed as 4 for speed reached.
F100 can be programmed to value desired in hz.

The RY relay will actuate when the VFD output frequency is greater than or equal to the F100 setting.

Schneider Electric Danmark

Se mere
Produkt:
Se mere
Produkt:

Brug for hjælp?

  • Produktvælger

    Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

  • Få et tilbud

    Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

  • Find forhandler

    Find den nærmeste Schneider Electric-distributør.

  • Hjælpecenter

    Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Få et tilbud
  • Find vores kontorer
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger