TS_DIAGNOSTIC_FLAGS for the BMXERT1604T is reporting an 137 error.

Issue
TS_DIAGNOSTIC_FLAGS for the BMXERT1604T  is reporting an 137 error.

Product Line
BMXERT1604T

Environment
Unity, OFS


Resolution
Displaying the TS_DIAGNOSTIC_FLAGS  in bits.  137(binary 10001001 ) shows that the  buffer is being reported as full.

This works as designed and it is not a defect in the BMXERT1604T

The following conditions can cause the buffer to be reported as full.
  • If the OPC server is not able to read the 'BMXERT1604T' event in time, the buffer will be reported as  full.
  • If the OPC server or EFB read ERT event is slower than the ERT event generated . the group number which store the events in the ERT will exceed 255,
Note: When the 'Buffer Full' bit is set, any new events will not be recorded.

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger