Vores varemærker

Impact-Company-Logo-English Black-01-177x54

Velkommen til Schneider Electrics website

Velkommen til vores website
		
Hvordan kan vi hjælpe dig i dag?
My Process Drive with Modbus serial is not indicating when my cable is disconnected or no Modbus communication?
Issue:
My Process Drive with  Modbus serial is not indicating when my cable is disconnected or no Modbus communication?

Product Line:
Altivar Machines

Environment:
All models and serial numbers

Cause:
Not default program to the drive.

Resolution:
Drive has to be configured for command and/or reference from Modbus or drive sees this as monitoring only, will not trip if it's not there.  Under Error/Warning Handling > Fieldbus Monitoring > SLL - Response to Modbus Interruption is set to Freewheel

Schneider Electric Danmark

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Få et tilbud
  • Find vores kontorer
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger