Why ports are not available for selection inside E-configurator modbus master scanner or How to setup modbus master scanner with modbus slave device with scadapack RTU ?

Yes its observed that when ports 1 or port 2 is to be selected inside modbus scanner of e-configurator through "ADD DEVICE"  button  Port selection field is empty and Port 1 and Port 2 is not available for selection.
To make it appear assign Port 1 function field in 'Ports' to Modbus master ( Modbus RTU) in Ports configuration . Refer screen shot below.



Later go to Modbus Scanner ---> Add Device ---> Select correct port like port 1 or port 2.




Final step is to configure scanner line inside scanner table with all the information related to modbus protocol to make communication successful.






Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger