Why Node-red embedded with Ecostruxure Augmented Operator Advisor stop few second after starting?

Symptom
After few second, you can see that Node-red stop working

How to diagnostic
When you start AOA, there is one MS-dos windows with a lot of information
ms doc description
In this exemple, you can see that the problem occur after flow starting and after more details about which flow create this error

How to solve the problem
This flow error avoid to start Node-red.
So, we will see how to restart with the previous working flow

Go to …Schneider-electric \ Ecostruxure Augmented Operator Advisor \ Node-red \ node-red home
file to update
In this folder you can see the current flow and also the last backup
The propose is to reuse the backup (the last working flow) and delete or rename the current flow (the flow creating node-red crash)
  1. Change the name or remove the flow named flow_W7FRN05933L.json
  2. Change the name of the backup .flow_W7FRN05933L.json.backup to  flow_W7FRN05933L.json
  3. Restart node-red

Schneider Electric Danmark

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger