Is it possible to connect one earth leakage circuit breaker with multiple ATV12 drives? How should that work?
Issue:
Is it possible to connect one earth leakage circuit breaker with multiple ATV12 drives? How should that work?

Product Line:
Altivar Machines, Altivar 12

Environment:
All models and serial numbers

Cause:
Documentation

Resolution:
The earth leakage breaker could be used with up to two or three drives maximum.
But to avoid the random tripping of the breaker and blindness of earth leakage circuit breaker it is recommended to use the RCD (Residual Current Device) full immunized due to the perturbation Type A(si).
Usually we recommend using one RCD by drive as describe in our catalogue (link here: https://www.se.com/us/en/download/document/8800CT1301/ )

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

  • Produktvælger

    Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

  • Få et tilbud

    Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

  • Find forhandler

    Find den nærmeste Schneider Electric-distributør.

  • Hjælpecenter

    Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Få et tilbud
  • Find vores kontorer
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger