Why does my Uni-telway connection fail to connect after installing Vijeo Designer V6.2 SP8?
Issue: The communication between a Magelis HMI and Premium PLC via the Uni-Teleway protocol fails to connect.

Product Line: Vijeo Designer V6.2 SP8 only

Resolution: A software bug in Vijeo Designer V6.2 SP8 caused the Uni-Telway driver to fail to connect a PLC. A hotfix has been released to resolve this issue. Please download the below hotfix.


NOTE: The latest service pack for Vijeo Designer 6.2 is currently SP12. If you would like to upgrade to SP12, please find more information here below:
https://www.se.com/us/en/faqs/FAQ000239885/


Schneider Electric Danmark

Bilag
SP8_Hotfix(6.2.8.2401_6.2.8.2401).zip [343.52 MB]
Web_Gate_Client_Files_SP8_Hotfix(6.2.8.2401_6.2.8.2401).zip [13.16 MB]
Runtime_For_Windows_SP8_Hotfix(6.2.8.2401_6.2.8.2401).zip [60.58 MB]
Se mere
Område:
Se mere
Område:

Brug for hjælp?

  • Produktvælger

    Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

  • Få et tilbud

    Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

  • Find forhandler

    Find den nærmeste Schneider Electric-distributør.

  • Hjælpecenter

    Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Få et tilbud
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger