What can cause an EEFI [EEPROM Control] Fault on an ATV340 series drive?

Article available in these languages: Spansk

Issue:
Is there a way to resolve an  EEFI [EEPROM Control] fault on an ATV340 series drive?

Product Line:
Altivar Machines, Altivar 340

Environment:
All models and serial numbers

Cause:
An error of the internal memory of the control block has been detected.

Resolution:
  • Verify the environment (electromagnetic compatibility).
  • Switch off the product.  Wait for the display to go blank, then wait 15 more seconds, then switch on the product.
  • Return to factory settings (*Only recommended if you have a backup of the  program stored in SoMove or an HMI)
  • Contact your local Schneider Electric representative.

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

  • Produktvælger

    Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

  • Få et tilbud

    Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

  • Find forhandler

    Find den nærmeste Schneider Electric-distributør.

  • Hjælpecenter

    Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Få et tilbud
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger