Issue:
Troubleshooting an Altivar Machine Drive with an Output Phase Fault, OPF1 or OPF2.
Product Line:
Altivar Machine Drive ATV12, ATV320, ATV340
Environment:
All serial numbers for Altivar Machine Drive
Cause:
N/A
Resolution:
[Single Output Phase Loss] OPF1
Principle:
- This fault appears when one motor phase is lost at the output of the inverter
- Loss of a phase at the output of the inverter
- Current is too low while running. Especially when starting and stopping where the frequency is lower.
- Check the connections between the inverter and the motor
- Check output current for an imbalance in one phase
[Output Phase Loss] OPF2
Principle:
- This fault appears when 3 motor phases are lost at the output of the inverter.
- Motor not connected or motor output power is too low.
- Motor or drive output contactor is open.
- Unstable motor currents.
- Check the connections between the inverter and motor.
- If using a motor contactor set parameter OPL (motor phase loss) to OAC or turn off OPL and use separate motor overloads
- To turn off OPL: [Complete settings] [Error/Warning handling] [OutPhase loss Assign]
- Test drive with no motor. Turn off OPL and run drive open circuit and test voltage on output for balancing
- Check motor parameters and try to apply autotuning if possible:
- Verify and optimize the following parameters: [IR compensation] UFr, [Nom Motor Voltage] UnS and [Rated mot. current] nCr and perform [Autotuning] tUn.
- Check or extend Output Phase Loss Time Detect [OutPhaseLoss Delay] Odt
- If intermittent or able to run at times without faulting then check motor currents.
Udgivet til: Schneider Electric Danmark






Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.