What causes the Precharge Capacitor Fault on Altivar Process drives?
Issue:
Altivar Process drives with Precharge Capacitor Fault

Product line:
Altivar Process, ATV600, ATV900

Environment:
All

Cause:
Unstable mains voltage
DC link capacitors lifetime exceeded

Resolution:

After switching on the DC Bus is charged by the rectifier bridge, if the DC bus is not stabilized within 5s (for 400ms +/- 5V at 400-480V OR +/- 8V at 690V) the fault CrF occurs.
The detection of the CrF fault is activated when VBUS voltage > USFH.


Power cycle the drive, make sure the display goes completely dead before turning back on
Measure the Mains Voltage coming into the drive and compare with the voltages shown in the Display menu
Check the internal wiring from the mains input up to the rectifier / AFE brick
Check the grounding

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

  • Produktvælger

    Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

  • Få et tilbud

    Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

  • Find forhandler

    Find den nærmeste Schneider Electric-distributør.

  • Hjælpecenter

    Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Få et tilbud
  • Find vores kontorer
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger