AS-P Modbus TCP Server do not provide data for HMI-STU Mobus Client
AS-P in version 1.9.4 can not respond for request which contain group of consecutive registers.
Exception Response FC03 - Illegal Data Address (Read Holding Register) - 00 00 00 00 00 06 FF 03 03 84 00 06 - 00 00 00 00 00 03 FF 83 02
(In this case client ask for 6 registers starting with register number 900)

Possible overwork:
1. Set HMI STU communication optimization mode to : Prefered Frame lenght = Minimum possible. Vijeo Designer, Equipment configuration.
2. Upgrade AS-P to version 2.0.3.45 (solution tested in ModScan32 tool)

Schneider Electric Danmark

Bilag
SBO Modbus Decoder.csv [150.79 KB]
Minimum possibe frame lenght.PNG.png [21.99 KB]
Se mere
Område:
Se mere
Område:

Brug for hjælp?

  • Produktvælger

    Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

  • Få et tilbud

    Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

  • Find forhandler

    Find den nærmeste Schneider Electric-distributør.

  • Hjælpecenter

    Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Få et tilbud
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger