PME 9.0 - New 3rd party device created with DTE does not work
Product Line
Power Monitoring Expert 9.0
Environment
DTE - Device Type Editor
Issue
The new devices created with DTE are not loading and you will see error messages in the System Log:
"Translator map file 'DEVICE_NAME.xml' not loaded due to previous error. Will retry."
"The attribute 'TimestampedByPlugin' on this element is not defined in the DTD/Schema." - (or some other attribute as well)
Cause
The modbus-schema.xml file in the config/translator folder is an old version and does not contain the specific attribute referred by the error log.
Resolution
Replace the modbus-schema.xml file in config/translator with the one from system/translator folder or from a healthy PME system.
Power Monitoring Expert 9.0
Environment
DTE - Device Type Editor
Issue
The new devices created with DTE are not loading and you will see error messages in the System Log:
"Translator map file 'DEVICE_NAME.xml' not loaded due to previous error. Will retry."
"The attribute 'TimestampedByPlugin' on this element is not defined in the DTD/Schema." - (or some other attribute as well)
Cause
The modbus-schema.xml file in the config/translator folder is an old version and does not contain the specific attribute referred by the error log.
Resolution
Replace the modbus-schema.xml file in config/translator with the one from system/translator folder or from a healthy PME system.
Udgivet til: Schneider Electric Danmark


Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.