Power Monitoring Expert - Power Quality Report is missing *Exceeds Tolerance indicator

Issue
The power quality report no longer indicates which events have exceeded tolerance and no longer tags them with "*Exceeds Tolerance"

Product Line
Power Monitoring Expert (PME) 8.2
Power Monitoring Expert (PME) 9.0

Cause
This indicator was removed in PME8.2 due to a UX decision.

Resolution
This has only been tested on a PME9.0 system.  It has not been tested on PME 8.2.

1) Navigate to the folder \Power Monitoring Expert\web\ReportDepot\ION Reports\ION Report Packs\StandardPowerQualityReports\
2) Create backup copy of the "Power Quality Report.rdlc".
3) Overwrite the "Power Quality Report.rdlc" with the new "Power Quality Report.rdlc" attached to this KB

This new rdlc has been modified to show "*Exceeds Tolerance".  This text has been hardcoded in English and will not translate into other languages.


Schneider Electric Danmark

Bilag
Hotfix_100454_ExceedsTolerancePQReport.zip [15.06 KB]
Se mere
Område:
Se mere
Område:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger