Issue
For Modbus Serial communication between M241/M251/M262 and Altivar 320, does the Polarization Resistor setting need to be turned on?
Product Line
Altivar 320, Modicon M241, Modicon M251, Modicon M262, EcoStruxure Machine Expert / SoMachine
Environment
Serial Communication setup in PLC configuration software
Resolution
Yes, polarization must be turned on in the PLC as per p27 of the ATV320 Modbus Manual:
(Document Reference#NVE41308)
https://www.se.com/ww/en/download/document/NVE41308/
To apply the setting, in EcoStruxure Machine Expert (or the previous version SoMachine):
For Modbus Serial communication between M241/M251/M262 and Altivar 320, does the Polarization Resistor setting need to be turned on?
Product Line
Altivar 320, Modicon M241, Modicon M251, Modicon M262, EcoStruxure Machine Expert / SoMachine
Environment
Serial Communication setup in PLC configuration software
Resolution
Yes, polarization must be turned on in the PLC as per p27 of the ATV320 Modbus Manual:
(Document Reference#NVE41308)
https://www.se.com/ww/en/download/document/NVE41308/
To apply the setting, in EcoStruxure Machine Expert (or the previous version SoMachine):
- In the Devices Tree of your EcoStruxure Machine Expert / SoMachine project, expand the tree for your PLC.
- Doubleclick on the Serial_Line_1 (or Serial_Line_2)node
- Under "Physical Medium", choose "Yes" in the dropdown list for Polarization Resistor
Udgivet til: Schneider Electric Danmark










Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.