Issue:
How can I configure an external fault using logic input in ATV320 drive?
Product Line:
ATV320 drive
Environment:
All Serial numbers
Cause:
Application requires an external fault via a logic input.
Resolution:
Yes, a logic input can be assigned to a external fault.
External Fault can be accessed: DRI- > CONF > FULL > FLT- > EtF- > EtF
Then assign (LI1) to (LI6), logic input that is not assigned to any other functions.
Logic can be configured (LEt) As LO [Active low] (LO) or HIG [Active high] (HIG)(default).
It defines the positive or negative logic of the input assigned to the detected fault.
Configure EPL [External fault mgt] for Type of stop in the event of an external fault.
How can I configure an external fault using logic input in ATV320 drive?
Product Line:
ATV320 drive
Environment:
All Serial numbers
Cause:
Application requires an external fault via a logic input.
Resolution:
Yes, a logic input can be assigned to a external fault.
External Fault can be accessed: DRI- > CONF > FULL > FLT- > EtF- > EtF
Then assign (LI1) to (LI6), logic input that is not assigned to any other functions.
Logic can be configured (LEt) As LO [Active low] (LO) or HIG [Active high] (HIG)(default).
It defines the positive or negative logic of the input assigned to the detected fault.
Configure EPL [External fault mgt] for Type of stop in the event of an external fault.
Udgivet til: Schneider Electric Danmark


Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.