EcoStruxure Hybrid DCS [2018] How to fix the error that 'A time stamped variable must be mapped on the address %SW73.7'

  1. Issue
Customer encountered an error “A time stamped variable must be mapped on the address %SW73.7 (SOE uncertain)” when building the executable.
  1. Product Line
Hybird DCS 2018
  1. Environment
Hybird DCS 2018, Unity Pro V13.0, Win10 64Bit SP1
  1. Resolution
  1. Refine the built program, create a test variable Bool type and assign address %SW73.7.
  2. Right click and go to customize columns, select time stamping and enable for this variable, and make it both edges.

After all, building the executable to check whether the error has been fixed.

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger