Issue
When changing tabs in Hierarchy Manager, the system tries to upload records. However, after a few minutes, it fails and shows the following message:

Loading records...
Failed to load data from the server. Please try again.
Product Line
Power Monitoring Expert 9.0
Environment
Hierarchy Manager
Cause
By default, the hierarchy manager has to upload records within 2 minutes. If it doesn't manage to upload within this time, it will fail.
Resolution
Change the Javascript file for HierarchyManager to increase the timeout. The file is:
...\Power Monitoring Expert\applications\HierarchyManager\Scripts\HierarchyManager\data.nodemodel.js
Find the following code snippet:
$.ajax({
type: "GET",
url: baseUrl,
timeout: 2*60*1000, // 2 minutes. Some hierarchy pages can take a long time to generate.
data: { nodeQuery: JSON.stringify(nodeQuery) },
dataType: "json",
success: onSuccess,
error: onError,
page: page
});
Change the timeout to 4*60*1000. This increases the timeout to 4 minutes.
*Note: This solution does not apply to versions of PME after PME 9.0
When changing tabs in Hierarchy Manager, the system tries to upload records. However, after a few minutes, it fails and shows the following message:
Loading records...
Failed to load data from the server. Please try again.
Product Line
Power Monitoring Expert 9.0
Environment
Hierarchy Manager
Cause
By default, the hierarchy manager has to upload records within 2 minutes. If it doesn't manage to upload within this time, it will fail.
Resolution
Change the Javascript file for HierarchyManager to increase the timeout. The file is:
...\Power Monitoring Expert\applications\HierarchyManager\Scripts\HierarchyManager\data.nodemodel.js
Find the following code snippet:
$.ajax({
type: "GET",
url: baseUrl,
timeout: 2*60*1000, // 2 minutes. Some hierarchy pages can take a long time to generate.
data: { nodeQuery: JSON.stringify(nodeQuery) },
dataType: "json",
success: onSuccess,
error: onError,
page: page
});
Change the timeout to 4*60*1000. This increases the timeout to 4 minutes.
*Note: This solution does not apply to versions of PME after PME 9.0
Udgivet til: Schneider Electric Danmark




Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.