Issue:
Is there a way to use the ATV212 drives with a Bonitron DC power supply for a site that only has single phase available?
Product line:
Altivar Building ATV212 Altivar 212
Cause:
Application single phase supply
Resolution:
The ATV212 are not suitable to be powered with single phase or by the DC bus. The DC power terminals are present on the drives; however, they're covered with glue to prevent connection. The DC bus terminals can only be used for measuring the DC bus.