What would cause the ATV320 drives to trip on OSF faults on powerup?

Article available in these languages: Spansk

Issue:
The ATV320 drives to trip on OSF faults on powerup?

Product Line:
ATV320

Environment:
All serial numbers

Cause:
Can not clear fault

Resolution:
To clear the OSF fault on powerup:
Set  UrES [Mains voltage]  to correct value of the line supply voltage.
Parameters described can be accessed by:

DRI- > CONF > FULL > FLT- > CLL
USb- [UNDERVOLTAGE MGT]   > enter
UrES [Mains voltage]  > enter
Enter the correct line voltage
If set to 380V change to 460V (or appropriate voltage per your application)

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

  • Produktvælger

    Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

  • Få et tilbud

    Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

  • Find forhandler

    Find den nærmeste Schneider Electric-distributør.

  • Hjælpecenter

    Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Få et tilbud
  • Find vores kontorer
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger