What can cause an InFN or error 23 fault on the ATV630 or ATV930 Process drives?
A communication interruption between the control block and the AFE or the BU bricks has been detected.- First check to see if they have wired their ethernet cable into the drives modbus ports.This normally cause the main display to go blank and control block goes offline.- Check the internal wiring between the control module line board and the AFE and or BUO's- Check the LED801 on the control board of the AFE brick) red means communication interruption.- Change the module link board.