Is it possible to use Resi9 MP on hollow wall?

Issue :
Installation of an enclosure Resi9 MP in a hollow wall.

Product Line :
Resi9 MP

Cause :
IEC 60670-1 standard constraint

Resolution :
Yes it's possible to use Resi MP on hollow wall, because we have a dedicated version with back part in GWT850 as requested by standard for hollow wall installation.

Note :
To select the right enclosure, please chose the commercial reference starting with MIP21, it contains hollow kit installation.
if you need a spare part for the hollow wall kit please refer to MIP99047.
Instruction Sheet of the hollow wall kit : BBV48374
Video : Resi9 MP - Flush Version Installation

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger