Issue :
If "SEL" bloc is executed with an input parameter with a size of 2 or 4 bytes and using it on a BMEx586040x M580 PLC, the CPU will go in exception with error code %SW124=0xEC10 because of a alignment problem in the optimized code of the bloc function "SEL".

Product line :
EcoStruxure Control Expert software tool with version V15.0 or lower.
Environment :
BMEx586040 with x= P or H
BMEH586040S
Resolution :
The issue will be fixed in a next revision of EcoStruxure Control Expert (> V15.0)
Workaround :
Two easy workaround exist :
1 : Duplicate the SEL bloc as shown below (size not equal to 2 or 4 bytes anymore) :

2 : Use conditional MOVE bloc instead of SEL as shown below :

If "SEL" bloc is executed with an input parameter with a size of 2 or 4 bytes and using it on a BMEx586040x M580 PLC, the CPU will go in exception with error code %SW124=0xEC10 because of a alignment problem in the optimized code of the bloc function "SEL".
Product line :
EcoStruxure Control Expert software tool with version V15.0 or lower.
Environment :
BMEx586040 with x= P or H
BMEH586040S
Resolution :
The issue will be fixed in a next revision of EcoStruxure Control Expert (> V15.0)
Workaround :
Two easy workaround exist :
1 : Duplicate the SEL bloc as shown below (size not equal to 2 or 4 bytes anymore) :
2 : Use conditional MOVE bloc instead of SEL as shown below :
Udgivet til: Schneider Electric Danmark


Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.