Modbus Ethernet Communication Setup for Modicon M221 in Vijeo Designer
To configure the Modbus Ethernet Server of the Modicon M221,1) Open the .SMBP project for the M221 in EcoStruxure Machine Expert-Basic2) Go to the green Configuration Tab3) Expand the "MyController" node4) Click on "ETH1" to select it5) Set up a Fixed IP Address, Subnet Mask, and Gateway Address as desired6) Ensure that "Modbus server enabled" has a tickmark in the checkbox
7) Download the changes to the PLC.In Vijeo Designer, to configure the HMI, take the following steps:1) In the Project tab of the Navigator window, right-click on IO Manager2) Add the Modbus TCP/IP Driver3) Double-click on the "ModbusEquipment01" node to bring up the "Equipment Configuration" dialog.4)Set the IP Address to match that of the M2215) Set the Unit ID to be 255 (that is the default Unit ID of the M221)6) Tick the checkbox for "IEC61131 Syntax" (this will use %M and %MW notation for Device Addresses)7) Under "Variables", set the "Double Word word order" to be "Low word first" (this is the word order for 32-bit Variables such as REAL types)
Udgivet til: Schneider Electric Danmark










Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.